FENECON Industrial XL Operating Instructions

1. About these instructions

These installation and service instructions are an integral part of the electrical energy storage system and must be kept in its immediate vicinity and accessible to personnel at all times. Furthermore, all documents listed in the appendix to these installation and service instructions and the operating instructions of the component manufacturers must be observed (link to Applicable documents).

Personnel must have carefully read and understood these operating instructions before starting any work.

TIP

Ensure that the latest version of the installation and service instructions is always used.

In this manual, the product is described as an electrical energy storage system, storage system or system. These terms refer to the battery energy storage system (BESS) supplied.

1.1. Manufacturer

FENECON GmbH
Gewerbepark 6
94547 Iggensbach
Germany

Phone:

+49 (0) 9903 6280 0

Fax:

+49 (0) 9903 6280 909

E-Mail:

aftersales.industrial@fenecon.de

Website:

www.fenecon.de

1.2. Formal information on installation and service instructions

© FENECON GmbH, 2026
All rights reserved.
Reproduction, even in part, is permitted only with the authorization of FENECON GmbH.
<<<

1.3. Version/revision of the installation and service instructions

Table 1. Version/revision
Version/Revision Change to the installation and service instructions Date Name

V0

Initial Draft

27.08.2025

FENECON GmbH

V1

Approval

01.09.2025

FENECON GmbH

V1

Publication on docs.fenecon.de

10.2025

FENECON PM

V2

Revision

11.2025

FENECON PM Industrial

V3

Revision Notes

03.2026

FENECON PM (MA)

V4

Introduction of ISO Warnings

06.2026

FENECON PM (MRH)

1.4. Darstellungskonventionen

1.4.1. Darstellungskonventionen — ISO-Warnhinweise

DANGER DANGER

Zeigt eine unmittelbar gefährliche Situation an, die — wenn sie nicht vermieden wird — den Tod oder eine schwere Verletzung zur Folge hat.

WARNING WARNING

Zeigt eine potenziell gefährliche Situation an, die — wenn sie nicht vermieden wird — den Tod oder schwere Verletzung zur Folge haben könnte.

CAUTION CAUTION

Zeigt eine potenziell gefährliche Situation an, die wenn sie nicht vermieden wird — eine geringfügige oder mäßige Verletzung zur Folge haben könnte.

NOTICE NOTICE

Zeigt eine potenziell gefährliche Situation an, die wenn sie nicht vermieden wird — Sachschäden zur Folge haben könnte.

SAFETY SAFETY

Diese Sicherheitshinweise zeigen Einrichtungen, Geräte oder Rettungswege an, die für die Rettung von Personen von Wichtigkeit sind.

1.4.2. Darstellungskonventionen — Ergänzende Informationen

HINWEIS:

Ergänzende Informationen.

1.5. Aufbau von Warnhinweisen

Warnhinweise schützen bei Beachtung vor möglichen Personen- und Sachschäden und stufen durch das Signalwort die Größe der Gefahr ein.

Warnhinweise sind entsprechend der SAFE-Methode aufgebaut:

Table 2. SAFE-Methode
Signalwort Bedeutung

S

Signalwort (GEFAHR, WARNUNG, VORSICHT oder ACHTUNG/HINWEIS)

A

Art und Quelle der Gefahr
Beschreibung der Gefahr und der Ursache der Gefahr

F

Folge
Beschreibung der möglichen Folge für Mensch, Tier und Umwelt, die durch die Gefahr eintreten kann

E

Entkommen
Handlungsempfehlungen, wie Gefahren vermieden werden können

DANGER DANGER

GEFAHR
Beschreibung von Art und Quelle der Gefahr und mögliche Folgen bei Missachtung.

  • Maßnahmen zur Vermeidung/Verbote.

1.6. Terms and abbreviations

The following terms and abbreviations are used in the installation and service instructions:

Table 3. Terms and abbreviations
Term/Abbreviation Meaning

AC

Alternating Current

ADR

Accord européen relatif au transport international des marchandises dangereuses par route
(European Agreement concerning the International Carriage of Dangerous Goods by Road)

BMA

Fire alarm system

BMS

Battery management system

FACP

Fire alarm control panel

CMB

Current Measurement Board

CSC

Cell Supervisor Circuit

DC

Direct Current

EMS

Energy Management System

grid operator

energy supply company

FEMS

FENECON Energy Management System

commissioning

commissioning

MCB

Circuit breaker

GCP

grid connection point (GCP)

NC

Normally Closed (NC) — normally closed/ normally closed contact

NMC

Nickel-Manganese-Cobalt

PE

Protective conductor

PV

Photovoltaic

RCD

Residual Current Device — Residual current device

RTE

Round-Trip-Efficiency — System efficiency
Ratio of discharged to charged energy.

SoC

State of Charge — State of Charge
The available capacity in a battery, expressed as a percentage of the nominal capacity.

VDE

German Association for Electrical, Electronic & Information Technologies e. V.

Widget

Component of Online Monitoring

INV

Inverter

1.7. Availability

Keep these operating and installation instructions or relevant parts of them within easy reach in the immediate vicinity of the product.

Pass these operating and installation instructions on to the new operator when handing over the product.

Technical changes, images and information in these installation and service instructions are subject to change without prior notice.

1.8. Serial number

Each electrical energy storage unit is marked with a unique serial number.
This consists of two parts:

  • the product number ("IXL010" for a system with FENECON batteries or "IXL0100" for a storage system with order integration)

  • a consecutive, six-digit numerical code (e. g. 000001)

The serial number is located on the type label and is used to uniquely identify the electrical energy storage system. It also provides information on the development status.
Changes in the development status that lead to deviations in operation or maintenance are indicated in these installation and service instructions by specifying the six-digit numerical code.

1.9. Type label

type label 2
Image 1. FENECON Industrial-XL — Type label

1.9.1. Position of the type label on the container

type label position w o extinguisher
Image 2. Type label on container without fire extinguishing system
type label position with extinguisher
Image 3. Type label on the container with fire extinguishing system

2. Safety

2.1. Intended use

The FENECON Industrial XL is an industrial energy storage system consisting of various components. These include, in particular, efficient inverters, the FENECON Energy Management System (FEMS) and battery packs (including BMS) as well as a liquid cooling system and room air conditioning. The FENECON Industrial XL large-scale system is offered with an inverter output of 1500 kW and a capacity of 4072 kWh. The energy storage system is used to store and supply electrical energy and is intended for connection to the 400 V/50 Hz low-voltage grid. Any use beyond this purpose is considered improper use.

The electrical energy storage must only be used if no safety-relevant functions are linked to its function.

Use in safety-critical applications, such as for supplying power to medical devices, is not permitted.

2.2. Field of application

The product is intended exclusively for use in the following areas of application:

  • Industrial sector

Any other use is not in accordance with the intended use.

The product is designed for use within Europe. For use outside Europe, please contact the FENECON Service.

2.3. Qualification of staff

To ensure that the system is used, installed and maintained as intended, only qualified personnel must be deployed. The area of responsibility, competence and supervision of the personnel must be precisely regulated by the operator.

The applicable regulations and rules of the German Social Accident Insurance (DGUV) must be observed during all activities on the electrical energy storage system, in particular during installation, operation, maintenance and servicing.

This includes, in particular, the provisions of DGUV Regulation 3 (Electrical systems and equipment) and other relevant DGUV regulations and information. The operator is responsible for ensuring that only instructed and qualified persons carry out work on the system and that the general occupational health and safety guidelines are observed.

Compliance with the DGUV regulations is the responsibility of the operator and is a prerequisite for safe and legally compliant operation of the system.

2.3.1. Trained electricians

Trained electricians means persons who:

  • are able to carry out work on electrical systems due to their technical training, experience and knowledge of the relevant standards and regulations.

  • have been commissioned and trained by the operator to carry out work on electrical systems and equipment of the battery system.

  • are familiar with how the battery system works.

  • recognize hazards and prevent them by taking appropriate protective measures.

  • Have access to all maintenance information.

2.3.2. Service personnel

Work that goes beyond connecting the system must only be carried out by the manufacturer’s specialist personnel. Other personnel are not authorized to carry out this work.

Service personnel include: The manufacturer’s personnel or specialist personnel instructed and authorized by FENECON GmbH, who must be requested by the operator for work on the system (e. g. assembly, repair, maintenance, work on the batteries, etc.).

2.4. Safety and protective devices

The safety devices must not be bypassed or switched off. Operating the system without or with defective protective devices is prohibited. The safety devices must always be freely accessible and must be checked regularly.

The safety devices are permanently integrated into the electrical energy storage system, so that no additional precautions are required during storage.

Maintenance of the safety devices is illustrated as part of the annual maintenance concept and must only be carried out by service personnel or authorized specialists.

All accesses to the electrical energy storage are locked with container doors. Access is only possible with a 4-digit numerical code. Only authorized specialist personnel must open the container.

The electrical energy storage system corresponds to protection class I. The installer of the system is responsible for the proper integration of the system into the local protection concept and for ensuring protection against electric shock in accordance with the applicable national installation standards.

2.4.1. Earthing connections/potential equalization

The electrical energy storage system has three earthing connections on the container and one earthing connection per inverter rack. The system also has two earth circuit connectors on the inverter racks.

The customer’s PE connection in the control cabinet is made via the -X1 supply terminal and can be connected with a maximum cross-section of 50 mm2.

All three PE connections on the customer side (1 x control cabinet, 2 x equipotential bonding rail — inverter rack) must be connected to the same equipotential bonding.

2.4.2. Lightning protection

If necessary, the operator is obliged to create a lightning protection concept for the electrical energy storage system and to integrate it into the lightning protection concept. The optional FENECON accessory package for lightning protection can be used for this purpose. If you are interested in option packages, please contact FENECON project at projekt@fenecon.de.

2.4.3. Fire alarm system

The FENECON Industrial XL is equipped with a fire alarm system. This is described in detail in the Fire alarm system section.

In the event of an alarm:

  1. Pre-alarm: First point smoke detector has tripped.

    • Contactors of the batteries open.

    • Section switches in the inverters open.

    • Signal to customer interface relay:

      • for electrical energy storage systems with serial number 000001 to 000020: Alarm.

      • for electrical energy storage systems from serial number 000021: Pre-alarm.

    • Warning light: Only a visual signaling device on the container triggers (warning light).

  1. Main alarm: Second point type smoke detector has tripped.

    • Signal to customer interface relay:

      • for electrical energy storage systems from serial number 000021: Main alarm.

    • Warning light: Only acoustic signal transmitter on the container triggers (siren).

2.4.4. Connection to fire alarm control panel (FACP)

The fire detection system can be connected to an external fire alarm control panel. The connection allows alarm and fault signals to be transmitted to an operator FACP.

Potential-free contacts are available for connecting to an external alarm panel
  • 1 x fire alarm system pre-alarm (NO)

  • 1 x main alarm (NO)

  • 1 x malfunction of the fire alarm system (NC)

  • 1 x fire extinguishing system tripped (NC) - optional

  • 1 x fire extinguishing system blocked (NC) - optional

    • Max. voltage: 30 V DC

    • Max. switching/continuous current: 3 A

These are located in the control cabinet on the bottom row of the DIN rails of the Industrial XL:

control cabinet interior bottom left marking
Image 4. Connection to FACP
Table 4. Connection to FACP — Terminal assignment

List item

=CONT+CC-X2

1

Terminal 5 → Relay for fire alarm system (pre-alarm)

2

Terminal 6 → Relay for fire alarm system (pre-alarm)

List item

=CONT+CC-X2

1

Terminal 7 → Relay for fire alarm system (main alarm)

2

Terminal 8 → Relay for fire alarm system (main alarm)

List item

=CONT+CC-X2

1

Terminal 9 → Relay for fire alarm system (fault)

2

Terminal 10 → Relay for fire alarm system (fault)

List item

=CONT+CC-X2

1

Terminal 11 → Relay for fire extinguishing system (tripped)

2

Terminal 12 → Relay for fire extinguishing system (tripped)

List item

=CONT+CC-X2

1

Terminal 13 → Relay for fire extinguishing system (blocked)

2

Terminal 14 → Relay for fire extinguishing system (blocked)

Connection cross-section (finely stranded, solid), min. 0.25 mm2 (AWG 22), max. 4 mm2 (AWG 12).

2.4.5. Faults in the fire detection system

  • In the event of faults in the fire detection system, the manufacturer’s installation and service instructions must be observed.

2.4.6. Maintenance of the fire detection system

  • Maintenance work on the fire alarm system must only be carried out by a VdS-approved specialist company or by qualified specialists for fire alarm systems (qualified specialist for fire alarm systems in accordance with DIN 14675).

2.5. Residual risks

The product is manufactured in accordance with the current state of the art and recognized safety principles, taking into account the relevant statutory regulations.

Nevertheless, handling the product may pose a risk to people and/or the environment.

DANGER DANGER

No unauthorized persons allowed!
Throughout the entire zone of danger, there is a risk of death or serious injury due to unexpected incidents.

  • Do not enter the zone of danger.

  • Switch off the electrical energy storage system before entering the dangerous areas.

  • Secure the electrical energy storage system against being switched on again.

  • Only authorized personnel are permitted to enter hazardous areas.

  • Stellen Sie bei einer Anlage im öffentlichen Raum durch eine entsprechende Einzäunung sicher, dass sich keine unbefugten Personen in den Bereichen um das Stromspeichersystem aufhalten.

DANGER DANGER

Danger of electric shock
Live components can cause death or serious injury if touched.

  • Do not touch any exposed live parts.

  • Do not open or manipulate any insulated components.

  • Avoid contact with live parts.

Work on live components of the electrical energy storage system must only be carried out by authorized service personnel.

WARNING WARNING

Risk of burns from hot surfaces
There is a risk of burns from hot wires and housing surfaces if there is direct contact with uninsulated surfaces or hot fluids.

  • Hazard points are marked with appropriate pictograms.

  • Avoid touching hot surfaces.

2.6. Safety instructions

2.6.1. General safety instructions for the electrical energy storage system

  • Select the installation site of the system so that a minimum clearances of 5 m from buildings or comparable structures is maintained.

  • Roofing of the electricity storage system and its components by the customer is not permitted.

  • The system’s protection specification against water is IP54. It is protected against splashing water on all sides, but not against water jets, temporary submersion or flooding (high water).
    Installation in areas at risk of flooding is technically possible, but is at the sole responsibility and risk of the operator.
    Any warranty and liability claims for damage caused by water ingress as a result of flooding, high water, water jets or standing water are excluded.

  • The electrical energy storage system must be installed on a level and load-bearing surface. The Industrial XL installation concept must be observed.

  • The operator must meet the requirements for the floor conditions, which can be found in the Industrial XL installation concept.

  • Read the instructions for installation and operation to avoid damage due to incorrect installation/operation.

  • Only operate the system under the specified environmental conditions.

  • The electrical energy storage system must only be used under the specified charging/discharging conditions (see Technical data).

  • Das Stromspeichersystem darf nur von befugten Personen bedient oder gewartet werden. Der Zugang ist für Kinder und unbefugte Personen untersagt. Tiere sind vom Stromspeicher fernzuhalten, da sie Kabel oder andere Komponenten beschädigen und dadurch Gefahren verursachen können. Stellen Sie dies insbesondere im öffentlichen Bereich durch eine entsprechende Einzäunung sicher.

  • Der Betreiber der Anlage ist verpflichtet, potenzielle Stolperstellen im Umfeld des Speichersystems zu identifizieren und zu bewerten.

  • The battery packs may have insufficient cell voltage after a long storage period. For more information, see section Storage.

  • The operator is prohibited from charging the battery packs with an external charger.

  • Do not expose the battery packs to high voltage.

  • Do not short-circuit/bridge the batteries.

  • Do not touch the battery plugs (+) and (-) directly with a wire or metal object (e. g. metal chain, hairpin). Excessive current can be generated in the event of a short circuit, which can lead to overheating, explosion or fire of the battery packs.

  • The battery packs must only be removed or replaced by service personnel.

  • Only transport the battery packs as hazardous goods.

  • Observe the applicable laws, regulations and standards when transporting the battery packs.

  • Before transport, ensure that the battery packs fulfill the indicated transport requirements (e.g. defined state of charge, secured connections, protective covers). This is the only way to ensure safe and compliant transportation.

  • Only use the battery packs as intended. Improper use can lead to overheating, explosion or fire of the battery packs.

  • Do not dismantle or modify the battery packs. The battery packs integrate a safety mechanism and a protective device, damage to which can lead to overheating, explosion and/or fire of the battery packs.

  • Protect the area of the electrical equipment and batteries from moisture and water.

  • Prevent water ingress when working on the electrical energy storage system.

  • Do not apply any mechanical force to the battery packs. The battery packs can be damaged and short circuits can occur, which can lead to overheating, explosion or fire of the battery packs. If damage to the battery packs is detected, contact FENECON Service immediately.

  • Do not crush, throw, drop or attempt to open the battery packs. Do not use the dropped battery pack and contact FENECON Service immediately.

  • Do not place any objects on the battery packs.

  • Do not step on the battery packs.

  • Do not use the battery packs if, during assembly, charging, normal operation and/or storage, changes in color, mechanical damage, leakage of liquids or deformation are detected or if evaporating gases can be smelled. If one of the cases mentioned here occurs, contact FENECON Service immediately.

  • If a battery exhibits unusual odours, excessive heating, a change in color or shape, leaking electrolyte solution or other abnormalities, it must be reported to authorized service personnel immediately. Otherwise there is a risk of overheating, explosion or fire. Only authorized service personnel must remove the battery from the battery tower.

  • Eye and skin contact with leaked electrolyte solution must be avoided. After contact with eyes or skin, rinse/clean immediately with water and seek medical attention. Delayed treatment can cause serious damage to health.

  • No work such as soldering, welding, drilling, grinding or other mechanical or thermal processing must be carried out on the battery packs or in their immediate vicinity. Work of this kind entails the risk of flying sparks, the formation of chips or the effects of heat. This can damage the insulator and the safety ventilation mechanism and lead to overheating, explosion or fire of the battery packs

2.6.2. Installation, operation and maintenance

Always observe the following safety instructions when installing, operating or maintaining the battery packs:

  • Installation work on the electrical energy storage system and making the cable connections must only be carried out by authorized and trained electricians.

  • Commissioning and maintenance work on the battery packs or the electrical energy storage system must only be carried out by authorized service personnel.

  • During assembly and maintenance work on the battery tower, service personnel must stand on dry insulating objects and must not wear any metal objects (e. g. watches, rings and necklaces) during maintenance work/operation.

  • Use insulated tools and wear personal protective equipment.

  • The battery packs can cause electric shock and burns due to short-circuit currents.

  • Do not touch two charged contacts with a potential difference.

  • Check that there is no voltage present on the battery pack using a two-pole voltage tester in accordance with DIN VDE 0682-401.

  • If an anomaly is detected, actuate the maintenance switch (if directly accessible).

  • Do not continue the maintenance work until the cause of the fault has been rectified.

2.6.3. Fire protection

  • Do not heat the battery packs. Excessive overheating can cause insulation materials to melt. This can cause the battery packs to explode or catch fire.

  • Do not expose the battery packs to open fire or dispose of them in a fire.

  • Do not set up or use any open sources of fire, heating or high temperatures in the vicinity of the electrical energy storage unit.

  • Keep the battery packs away from sources of heat and fire, flammable, explosive and chemical materials.

  • Avoid contact between the battery packs and conductive objects (e. g. wires).

  • Use the operating fluids and coolants specified by the manufacturer.

  • Maintain the prescribed clearances around the electrical energy storage system in accordance with the installation concept.

  • Fire, open light and smoking in the installation area of the electrical energy storage system is prohibited.

  • The fire alarm system must only be serviced by service personnel.

2.7. Behavior in emergency situations

In an emergency (e. g. smoke, fire, unusual noises or odors), proceed as follows:

  1. Disconnect the electrical energy storage system from the grid as far as safely possible.

  2. Leave the danger zone immediately.

  3. Cordon off the danger zone and prevent access.

  4. Alert the relevant emergency services.

  5. Warn neighbors and other persons at risk immediately.

  6. Do not attempt to extinguish the fire yourself. Extinguishing must only be carried out by the emergency services using suitable means (see fire protection in Applicable documents).

  7. Alert a doctor in the event of injuries.

2.8. Reasonably foreseeable misuse

All applications that do not fall within the scope of the intended use are considered misuse.

2.8.1. Safety rules

Work on live parts is generally not permitted. Electrical work must only be carried out by qualified electricians.

The following safety rules must be observed for all work on electrical components:

  1. Disconnect.

  2. Secure against restarting.

  3. Check that there is no voltage.

  4. Earth and short-circuit.

  5. Cover or shield neighboring and live parts.

Non-compliance with the safety rules is considered a reasonably foreseeable misuse.

2.9. Other misuses

Misuses are:

  • improper transportation, installation, assembly, trial operation or operation that may damage the product,

  • change in the specified technical characteristics, including the individual components,

  • change or deviation of the connected load,

  • functional or structural changes,

  • Operating the product in a faulty or defective condition,

  • improper repairs,

  • use by untrained persons (instruction in accordance with the installation and service instructions is provided by the operator),

  • operation without safety devices or with defective safety devices,

  • disregarding the information in the original operating instructions,

  • unauthorized access via the control unit or the network,

  • Fire, open light and smoking in the vicinity of the storage system,

  • insufficient ventilation,

  • unauthorized changes and actions to the electrical energy storage system,

  • Private use,

  • Use as mobile energy storage,

  • Direct use in a PV system.

    • NOTE: Only AC-side feed-in is possible.

2.10. Pictograms

Pictograms on the system indicate dangers, prohibitions and instructions. Illegible or missing pictograms must be replaced by new ones.

Table 5. Pictograms — Warning signs
Pictogram Meaning Location
w012

Warning: Dangerous Electrical Voltage

Pictogram on the housing and labeling of components where it is not immediately apparent that they contain electrical equipment that could pose a risk of electric shock.

w023

Warning: Corrosive Substances

On the battery packs.

grounding

Ground before use

In the area of the earthing connections (e. g. on the container)

electro bin

Waste electrical and electronic equipment does not belong in household trash but must be collected and disposed of separately!

On the battery packs.

w024

Warning: Risk of hand injury

w017

Warning: Hot Surface

w001

General warning symbol

w026

Warning regarding hazards associated with charging batteries

On the battery packs.

Table 6. Pictograms
Pictogram Meaning Position
p001

General prohibition sign

p003

Flame/ignition source; fire, open ignition sources, and smoking prohibited

p007

No entry for persons with pacemakers or implanted defibrillators

p080

Unauthorized entry prohibited

m002

Read the manual and follow the instructions before assembly and use

m014

Wear protective headgear.

m008

Wear safety boots or shoes.

m009

Wear protective gloves.

2.11. Operating materials/equipment

2.11.1. Electrolyte solution of the battery packs

WARNING WARNING

Danger of serious eye and skin damage, as well as danger of blindness

  • After skin contact: Immediately wash skin thoroughly with neutralizing soap and consult a doctor if skin irritation persists.

  • After eye contact: Immediately flush eye(s) with running water for 15 minutes and seek medical advice.

Delayed treatment can cause serious damage to health.

  • Electrolyte solution is used in the battery packs (NMC).

  • The electrolyte solution in the battery packs is a clear liquid and has a characteristic odor of organic solvents.

  • The electrolyte solution may crystallize after discharge.

  • The electrolyte solution in the battery packs is flammable and corrosive.

  • Contact with electrolyte solution can cause severe burns to the skin and damage to the eyes.

  • Do not inhale the vapors.

  • Leave the contaminated area immediately after inhaling the vapors.

  • If the electrolyte solution is swallowed, induce vomiting.

TIP

Further information on the electrolyte solution can be found in the safety data sheet for the batteries.

2.11.2. Agent of the cooling system

TIP

The coolant used in the cooling system is R513a.

Observe the relevant supplier documentation.

  • Contains pressurized gas. The container may explode if heated.

  • Rapid evaporation or contact with the liquid can cause frostbite.

  • The vapors are heavier than air and can accumulate in deep areas, reducing the oxygen concentration.

  • If concentrations are too high, anesthetic effects may occur.

  • Misuse or intentional inhalation can be fatal without alarming symptoms due to effects on the heart.

  • Inhalation of the coolant can cause cardiac arrhythmia.

  • Thermal decomposition can produce toxic and corrosive compounds.

2.11.3. Electrical equipment

  • Work on electrical equipment must only be carried out by trained electricians.

  • Maintenance work must only be carried out by trained specialist personnel (service personnel).

  • Before starting work on the electrical energy storage system, visually check for insulation and housing damage.

  • Regularly carry out checks for insulation and container/housing damage.

  • The system must never be operated with faulty or non-operational electrical connections.

  • Only insulated tools must be used for maintenance on uninsulated conductors and terminals.

  • Control cabinets (e. g. inverter housing) must always be kept locked. Only authorized personnel with appropriate training and safety instructions (e. g. service personnel) should be allowed access.

  • The inspection and maintenance intervals for the electrical components specified by the manufacturer must be observed. Details can be found in the maintenance instructions.

  • To avoid damage, lay supply lines without crushing and shearing points.

  • If the main switch is disconnected, specially marked external circuits may still be live!

  • Dangerous residual voltages may still be present on some equipment (e. g. inverters) with an electrical intermediate circuit for a certain period of time after disconnection. Check that there is no voltage on these systems before starting work.

2.12. Notes on occupational health and safety

The obligations arising from occupational health and safety must be implemented by the operator of the low-voltage equipment.

Operator obligations in relation to the use of the product:

  • Make these installation and service instructions or extracts thereof available to persons who carry out tasks with or in connection with the product.

  • Provide the Applicable documents to these persons.

  • Instruction of persons with regard to the intended use as well as the prohibited use.

  • Instruction of persons with regard to safety devices and supplementary protective devices.

  • Instruction of persons with regard to all residual risks.

2.13. Personal protective equipment

Depending on the work on the system, personal protective equipment must be worn:

  • Protective footwear.

  • Protective gloves, cut-resistant if necessary.

  • Protective eyewear.

  • Protective headgear.

  • Safety vest.

  • Fall protection.

Carry a first aid kit with you.

2.14. Spare and wear parts

The use of spare and wear parts from third-party manufacturers can lead to risks. Use only original parts or spare and wear parts approved by the manufacturer. Observe the instructions for spare parts.

TIP

Contact the manufacturer for further information.

2.15. IT security

FENECON systems and their applications communicate and operate without an internet connection. The individual system components (inverters, batteries, etc.) are not directly connected to the internet or accessible from the internet. Sensitive communication via the internet is processed exclusively via certificate-based TLS encryption.

  • Access to the programming levels is not barrier-free and is accessible at different levels depending on the qualifications of the operating personnel. Safety-relevant program changes require additional verification.

  • FENECON processes energy data of European customers exclusively on servers in Germany and these are subject to the data protection regulations applicable in this country.

  • The software used is checked using automated tools and processes established during development in order to keep it up to date and to rectify security-relevant vulnerabilities at short notice. Updates for FEMS are provided free of charge for life.

3. Technical data

3.1. General

xl setup front
Image 5. Electrical energy storage system — Overview

3.2. System overview

3.2.1. Physical overview

xl setup front numbered
Image 6. Physical overview — front
xl setup rear numbered
Image 7. Physical overview — rear
Table 7. Physical overview

1

Battery container

3

Inverter rack next to cooling system

2

Inverter rack front

4

HYDAC liquid cooling system

3.3. Battery container

xl open doors numbered 2
Image 8. Battery container (open)
control cabinet area numbered
Image 9. View — Control cabinet (open)
Table 8. Battery container (open)

1

Battery rack 1

8

Cable bushing — Inverter

2

Battery rack 2

9

F2B box

3

Battery rack 3

10

Explosion vent panels

4

Control cabinet

11

Room air conditioning system

5

Manual activation switch

12

Cable bushings — Inverter

6

Visual and acoustic signaling device

13

Overvoltage protection — Inverter communication

7

Cable bushings — Control cabinet

3.3.1. Steel construction — Battery containers

xl steel construction
Image 10. Steel construction — Battery containers

The underlying steel construction of the FENECON Industrial XL has been statically tested and meets all requirements.
The surface coating is RAL9010 pure white in accordance with C4H.

The weight of the steel structure is 6,340 kg.

3.3.2. Control cabinet

control cabinet ext numbered
Image 11. Control cabinet components (external)
Table 9. Control cabinet components (external)

1

Service socket

5

Container lighting OFF/ON

2

Service network interface

6

Maintenance switch

3

CAN bus interface Rack 1-3

7

Buffering 24 V Rack 1-3 OFF/ON

4

Main switch

8

Indicator lights: green (operation), yellow (warning), red (fault)

control cabinet interior numbered
Image 12. Control cabinet components (internal)
Table 10. Control cabinet components (internal)

1

AC feed-in/interface — Customer

6

Network

2

Interface — Container/air conditioning

7

24 V distribution — F2B

3

AC supply

8

Control cabinet thermostat

4

Interface — Control cabinet door

9

24 V supply — F2B

5

24 V distribution (internal)

10

FEMS/IO system

3.3.3. AC connection area

control cabinet interior bottom left blue marking
Image 13. AC connection area
  • AC connection (customer-side)

  • Max. connection cross-section: 50 mm2

  • Pre-fuse: 80 A, operating class: gG

  • Possible network configurations: TN-C / TN-S

TIP

  • For a TN-C grid, use the optionally enclosed jumper between -X1.9 and -X1.10.

  • If a PEN conductor is used, an N conductor must not be connected.

3.3.4. DC connection area

xl connection area numbered
Image 14. DC connection area
Table 11. DC connection area

1

DC connection plate for battery tower 1

3

DC connection plate for battery tower 3

2

DC connection plate for battery tower 2

3.3.5. Feedthroughs

xl rear view numbered
Image 15. Feedthroughs
Table 12. Feedthroughs

1

Feedthroughs — Control cabinet

3

Feedthroughs — Cooling system

2

Feedthroughs — Inverter

aux supply and comm glands numbered
Image 16. Feedthroughs — Control cabinet
Table 13. Feedthroughs — Control cabinet

1

AC supply — customer, max. 50 mm2
(cable diameter 34-48 mm)

3

internet — customer
(2 x cable diameter 13-21 mm)

2

Communication connection — Customer

  1. Inverter release

  2. RS485 bus interface

  3. Fire alarm/extinguishing system (7 x cable diameter 9-17 mm)

DC glands numbered
Image 17. Cable glands — Inverters
Table 14. Cable glands — Inverters

1

DC inverter rack 1/front

3

DC inverter rack 2/cooling

2

Communication — Inverter rack 1/front

4

Communication — Inverter rack 2/cooling

climate connector ext numbered
Image 18. Feedthroughs — Cooling system
Table 15. Feedthroughs — Cooling system

1

Cooling system supply and return lines

3

Communication — Cooling system

2

AC supply — Cooling system

4

Maintenance access — Connection area

3.3.6. Battery tower

xl battery rack numbered
Image 19. Battery tower
Table 16. Battery tower

1

Steel frame

6

Grounding cable — Battery

2

Battery pack

7

Serial cooling connection between battery strings

3

HV800 box (high-voltage 800 V box) on carrier plate

8

Communication connection battery to F2B

4

Amphenol DC connector on batteries

9

F2B-to-HV800 communication connection

5

F2B box (FEMS-2-Battery box) on carrier plate

10

Rollers of the battery tower

3.3.7. Battery

xl battery numbered
Image 20. Battery — front view
xl battery rear numbered
Image 21. Battery — rear view
Table 17. Battery

1

Cooling water connection supply and return

3

Front HV connections

2

Additional HV connection

4

Additional HV connection (rear)

3.3.8. Cooling system distribution

xl cooler pipes
Image 22. Cooling system distribution
Table 18. Cooling system distribution

1

Cooling system supply and return lines for battery towers 1 and 2

3

Junction box of the cooling system distribution at the container for supply and return

2

Cooling system supply and return lines for battery tower 3

3.3.9. Fire alarm system (FAS)

The fire alarm system is installed and checked at the factory. Maintenance and service work on the fire alarm system must only be carried out by authorized specialist personnel. Safety-relevant information can be found in the Safety section.

In the event of an alarm or malfunction, contact the FENECON service personnel.

TIP

To restart the system after a false alarm/fault, acknowledge the fire detection system alarm on site.

TIP

Trip test alarms with test gas. Use test gas [ALL081] Test gas test aerosol 918-5 250 ml for this purpose.

FAS FACP
Image 23. Fire alarm system — Fire alarm control panel
FAS multi sensor
Image 24. Fire alarm system — Multi-detector sensor
FAS switch and transmitter
Image 25. Fire alarm system - switches and signaling devices
Table 19. Fire alarm system

1

Fire alarm control unit

4

Manual activation switch

2

Multi-detector sensor

5

Audible and visual signaling device

3

Multi-detector sensor

3.3.10. Lightning protection system

lightning protection
Image 26. Lightning protection system
Table 20. Lightning protection system

1

Lightning rods

3

Wall mountings

2

Support tubes

4

Insulated cables

3.4. Inverter rack

inverter rack numbered
Image 27. Inverter rack
Table 21. Inverter rack

1

Steel frame

5

Roof

2

Vibration damper

6

Lifting eyebolts (4 x per inverter rack)

3

Inverter
(9 per inverter rack)

7

Cable ladders

4

Lifting points for transportation
(4 x per inverter rack)

3.4.1. Steel construction — Inverter rack

inverter rack steel construction
Image 28. Steel construction — Inverter rack

The steel construction of the FENECON Industrial XL inverter rack has been statically tested and meets all requirements.
The surface coating corresponds to corrosion protection class C4H and is finished in RAL 9010 pure white.
The weight of the steel structure is 640 kg.

3.4.2. Inverter

KACO bp 92 inverter
Image 29. Inverter
inverter descriptions
Image 30. Inverter — Junction box

3.4.3. Cable ladder

inverter rack DC cabling
Image 31. Cable ladder

The color coding of the cables in the picture above is as follows:

  • Orange = AC cable of the customer

  • Black = DC and communication cable

  • Green/yellow = grounding cable

The DC cables are laid in the lower area of the cable ladders.
The customer’s AC cables are laid in the upper area.

  • Single wires with a maximum cross-section of 150 mm2 are permitted.

  • The cable ladder is not designed for AC feed lines in multiple cable bundles.

The side channels are intended for the customer feed of the AC cables. The middle channel is intended for the DC and communication connections to the battery container.

inverter rack equipot bar
Image 32. Equipotential bonding bar

The customer can connect up to two protective conductors from the AC power supply to the equipotential bonding bar on the inverter rack (see image). Using two protective conductor cables allows the required cross-sectional area to be divided accordingly. The dual configuration of the protective conductor connections ensures redundancy and thus provides additional safety.

3.5. Cooling system

ccu numbered
Image 33. Cooling system
Table 22. Cooling system

1

Drip tray

6

Electrical interface — Power supply

2

Roof

7

Temperature controller

3

Connection/Flow

8

Main switch

4

Connection/Return

9

Cover plate — Maintenance access

5

Electrical interface — Signal

3.6. Cable bridges

cable bridge
Image 34. Cable bridges

The cable bridges between the inverter racks and the container are installed by the service personnel during commissioning. The DC and communication cables of the inverter racks are routed to the inverter connection of the container via these cable bridges.

NOTICE NOTICE

Possible damage to equipment due to improper cable installation.

  • When laying the cables, make sure that they are only laid next to each other.

  • Overlapping of cables is not permitted.

4. Assembly preparation

4.1. General description

standard sys config
Image 35. Standardized system configuration

Standardized system configuration, generally valid for all FENECON industrial storage systems. Details vary depending on the electrical energy storage system. This system configuration can be an example for the application of self-consumption optimization.

Residual risks:

DANGER DANGER

Risk of death due to malfunction
A malfunction can result in serious injury or death.

Before switching on the system, make sure that

  • there are no persons in the zone of danger.

  • all safety devices are installed and active.

NOTICE NOTICE

Risk of property damage due to malfunction

  • Observe the specifications and instructions in the operating/installation instructions of the respective manufacturer.

4.2. Scope of delivery

Table 23. Scope of delivery
List item Component Amount Item no. Comment

1

Container incl. 36 batteries, room air conditioner and cabling

1

BGI0764 (pre-series)

Transport reinforcement of the container back to FENECON

2

Inverter rack front with 9 inverters each (KACO bp 92.0 TL3-S)

1

BGI0387

3

Inverter rack climate with 9 inverters each (KACO bp 92.0 TL3-S)

1

BGI0388

4

HYDAC cooling system

1

ZUI2191

5

Drip tray and roof for the climate control unit

1

ZUI2192

6

Cable jumper set inverter rack to container

1

BGI0782

7

Cooling cable jumper set

1

BGI0788

8

Drums with coolant (water/glycol) 220 liters each

2

ZUI2841

Return to FENECON

9

Canisters with coolant (water/glycol) 30 liters each

1

ZUS830

Return to FENECON

10

Grid box with cable bridges and hose set

1

BGI0786 (pre-series)

Return to FENECON

Software licenses for operating the system are not included in the standard scope of delivery. The applications Read and Write Access (REST/JSON and Modbus/TCP, Self-Consumption Optimization, Peak Shaving (phase-accurate) and Time Slot Peak Shaving can be purchased optionally. These can be installed both retrospectively and directly during commissioning. The instructions for FEMS applications for the electrical energy storage system can be found at docs.fenecon.de.

4.3. Tools/machines required

The following tools are required for assembly of the system components:

Table 24. Tools required
Description Comment

Crane

Crane with chain slings
(minimum length of chain sling 6.5 m)
(container weight 32 t fully loaded)
Lifting instructions — Container must be observed.
Lifting instructions — Inverter rack must be observed.

Multimeter

Socket wrench set/ratchet box

Hexagon socket wrench set

Measuring tape/measuring device for setting up the components

Toolbox for electrician

5. Assembly — General

The AC connections and inverters are assembled and installed by the operator. Please make an appointment in advance with your contact person at FENECON for the subsequent commissioning.

FENECON GmbH
Gewerbepark 6
94547 Iggensbach
GERMANY
+49 (0) 9903 6280 0
aftersales.industrial@fenecon.de

Residual risks:

DANGER DANGER

Risk of death due to malfunction
A malfunction can result in serious injury or death.

Before switching on the system, make sure that:

  • there are no persons in the zone of danger.

  • all safety devices are installed and active.

NOTICE NOTICE

Possible equipment damage due to improper operation
Improper operation can cause damage to the system.

  • Observe the specifications and instructions in the operating/installation instructions of the respective manufacturer.

The following components must be installed or connected by the operator:

  • Container

  • 2 inverter racks with 9 inverters each

  • Cooling system

TIP

Before installation, check carefully whether the products are damaged and whether all accessories listed in the scope of delivery are included. If a part is missing or damaged, contact the manufacturer/dealer.

5.1. Select installation site

5.1.1. Installation site

  • Install the system outdoors.

  • Avoid dirt and dust during assembly.

  • Do not install the electrical energy storage system in an area that is at risk of flooding.

  • Do not install the electrical energy storage system where the ambient conditions are outside the operating requirements.
    (Max. 2000 m above sea level — For more information see: Section: Technical data).

  • Keep the batteries away from heat sources and fire.

  • The electrical energy storage system must be set up in such a way that only authorized personnel have access to it.

The operator of the system is responsible for selecting and preparing a suitable installation site for the energy storage system. It must be ensured that the ground is suitable for the use of a crane. The lifting instructions must be observed for the design of the crane and the lifting beam. Sufficient clearance must also be ensured in front of the container. The requirements for the installation site from the FENECON installation concept must be met.

The BESS FENECON Industrial XL must be installed and operated outdoors.

5.2. Assembly steps

xl setup rear
Image 36. Electrical energy storage system — rear view
NOTICE NOTICE

Equipment damage if lifting instructions are not observed

  • Follow the instructions provided for unloading the container, the inverter racks and the liquid cooling system.

5.2.1. Unload container

  1. Use a crane to unload the container.

  2. Please observe the Lifting instructions for positioning the container.

  3. Observe the foundation and load transfer recommendations for placing the container.

5.2.2. Unloading the inverter racks

  1. Use a crane to unload the inverter racks.

  2. Be sure to observe the Lifting instructions for unloading the inverter racks.

  3. Observe the foundation and load transfer recommendations for positioning the inverter racks.

5.2.3. Positioning and setting up the liquid cooling system

  1. Use a crane to unload the HYDAC cooling system.

  2. Always follow the manufacturer’s lifting instructions for unloading the HYDAC cooling system! See Applicable documents.

  3. Observe the foundation and load transfer recommendation for positioning the HYDAC cooling system.

5.3. Setting up the system

  1. Set up and align the drip tray.

  2. Place the HYDAC liquid cooling system on the drip tray.

  3. Install the roof on the liquid cooling system.

5.3.1. Install equipotential bonding/earthing

An earthing connection can be made to the container and the inverter racks. The electrical energy storage system must be integrated into the on-site lightning protection concept and the corresponding earthing and equipotential bonding cables must be connected to the marked points. The instructions in the installation concept must be observed.

5.3.2. Wiring the AC/DC connections

The AC supply for the container must be designed by the customer and is therefore not included in the scope of delivery.

CAUTION CAUTION

Danger due to improper wiring of the AC/DC connections

  • Lay single wires!

6. Network connection

The network connection and communication to FENECON Industrial XL is implemented as follows by default:

6.1. Standard setup — Internet via fiber optics

xl fems interface fibre
Image 37. Internet via fiber optics

Internet — Standard via SFP: Only one connection via optical fiber is required. The internet connection must be established in accordance with the information in the section Technical documentation FEMS. Communication with the power plant controller and controller of the energy storage system is also implemented via this interface as standard.

The SFP+ module for the fiber optic connection must be provided by the customer. For technical queries or further coordination, please contact FENECON project management.

Superordinate EMS (MB TCP): If the internet connection is to be separated from the rest of the network, establish a physical separation via a second Ethernet connection. This allows the energy storage system to be integrated into a local network without having to establish an internet connection.

The separate internet connection is still necessary!

6.2. Internet via ETH

If the internet connection is not to be established via fiber optic, but via Ethernet, it is necessary to purchase the additional package "Internet via ETH". This consists of an additional overvoltage protection, an ETH/SFP module and an additional connection cable. These components must be installed according to the Industrial XL instructions. Please note the maximum cable length of the option.

xl fems interface eth
Image 38. Internet via ETH

The option Superordinate EMS (MB TCP) remains unaffected by this and can be set up in the same way as in the previous section.

6.3. General information

  • There is no option to provide the internet via a SIM card to be integrated.

  • An unrestricted internet connection is required to ensure optimal operation.

  • The maximum cable lengths of the supply lines used must always be observed.

  • The Ethernet cable must NOT be connected directly to the system router, only SFP!

  • The system is operated with the FEMS App Modbus/TCP write access by default.

7. Initial commissioning

The initial commissioning is carried out by FENECON GmbH. Please arrange an appointment for commissioning in advance with your contact person at FENECON GmbH.

FENECON GmbH
Gewerbepark 6
94547 Iggensbach
GERMANY
+49 (0) 9903 6280 0
aftersales.industrial@fenecon.de

Residual risks:

DANGER DANGER

Risk of death due to malfunction.
Malfunction can result in serious injury or death.

  • Before switching on the individual components, read the specifications and instructions from the respective manufacturer’s documentation.

  • Before switching on, make sure that there are no persons in the zone of danger.

  • Ensure that all safety devices are installed and active.

NOTICE NOTICE

Possible property damage due to malfunction

  • Before switching on the system, ensure that the specifications and instructions in the operating/installation instructions of the respective manufacturer are observed.

8. FEMS — FENECON Energy Management System

8.1. Technical documentation — FEMS

The technical documentation of FEMS must be observed; this can also be found on the FENECON website at: www.docs.fenecon.de/en.

  1. Internet connection
    A permanent internet connection for the FEMS is recommended and is necessary for commissioning. In principle, offline operation is also possible. In this case, however, the following functions cannot be used:
    Remote commissioning, system updates, installation of new FEMS Apps, transfer of measurement data to FENECON servers for remote access, use of Online Monitoring via the FENECON portal access (e. g. for on the go via smartphone), maintenance access for FENECON Service employees, use of FEMS Apps with third-party services via the internet (e. g. Time-of-use tariffs).

  1. Network configuration
    In the standard configuration, FEMS obtains the IP address via a DHCP server (e. g. FritzBox). The network configuration can also be adjusted in Online Monitoring under Settings & Network configuration. More information can be found here.

  1. System update
    The system is regularly updated as part of software updates. These updates can be installed via the Settings & FEMS system update tab.

8.2. Online Monitoring

The FEMS Online Monitoring is used to visualize all energy flows in the system. The energy monitor shows live data on grid withdrawal or grid feed-in, PV production, charging/discharging of the battery storage system and electricity consumption. Other widgets show the percentage of self-sufficiency and Self-consumption. In addition, the individual widgets offer a detailed view, which can also be used to view the performance values with phase accuracy.

In addition to the pure information display, Online Monitoring also lists all additionally purchased FEMS extensions, such as phase-accurate Peak Shaving, self-consumption optimization, Time Slot Peak Shaving. Their functionality can be controlled via the corresponding widget. The integration of a PV system or other generators is also possible with the FEM112 package.

In addition to the live view, the history offers the option of selecting self-selected time periods for Online Monitoring.
The status of both the overall system and the individual components can be monitored at any time using the info icon.

The technical documentation of FEMS must be observed; this is also available on the FENECON website at: www.docs.fenecon.de/en/.

8.3. Access data

Access to FEMS Online Monitoring is separated according to end customer and installer.

8.4. Overview

inl online monitoring
Image 39. FEMS Online Monitoring

9. Troubleshooting

Residual risks:

NOTICE NOTICE

Risk of equipment damage due to unknown malfunctions
Unknown malfunctions and attempts to fix them may result in damage to the product.

  • If there is a fault that is not displayed in the fault message list, inform customer service.

9.1. FEMS Online Monitoring

The system status can be checked after logging in at the top right using the color of the icon.

9.1.1. Fault display

Table 25. Fault display
ok

System status: Everything is OK

warning

System status: Warning

error

System status: Error (Fault)

9.1.2. Troubleshooting

Table 26. Troubleshooting
fems troubleshooting 1

For a detailed overview of an existing warning or error, click on the exclamation mark in the top right-hand corner.

fems troubleshooting 2

You can use the scroll bar to examine the origin of the warning or error in more detail.
In this example, the error lies with the controller used.

fems troubleshooting 3

Clicking on the icon (down arrow) displays a more detailed error description depending on the error.

In the example above, an incorrect reference for the grid meter was intentionally entered for test purposes, which is why the controller execution fails.
The FENECON Service must be contacted to rectify errors.

fems offline

Under certain circumstances, the FEMS may not be accessible and the adjacent error message may appear.

If the FEMS is offline, follow the steps displayed below the message.

9.2. FENECON Service

These installation and service instructions only contain work that can be carried out without specialist knowledge of the manufacturer.

Work that is not described must only be carried out by authorized service personnel. Contact customer service to change parameters and programs.

If the energy storage system malfunctions, contact the FENECON Service:

Phone: +49 (0) 9903 6280 0
E-mail: aftersales.industrial@fenecon.de

9.2.1. Details for the FENECON Service

The following information must be provided for the FENECON Service:

  • Device type/configuration.

  • FEMS number.

  • Serial number.

  • The currently installed software version.

  • Ticket number from previous faults (if available).

  • Inverter error code (if available).

The information can be found on the type label and in the system profile in Online Monitoring.

9.2.2. Service times

Monday to Thursday:

08:00 am to 12:00 pm | 1:00 pm to 5:00 pm

Friday:

08:00 am to 12:00 pm | 1:00 pm to 3:00 pm

10. Technical maintenance

10.1. Tests and inspections

WARNING WARNING

Risk of malfunctioning due to improperly performed inspections.

  • Inspections serve to determine the safety of the product.

  • Only have inspection work carried out by trained and qualified specialists.

  • Instruct the authorized electricians to observe the maintenance instructions for all individual components.

Check the product and the cables regularly for visible external damage. If components are defective, contact the FENECON Service. Repairs must only be carried out by a qualified electrician.

10.2. Cleaning

NOTICE NOTICE

Risk of damage to the system from improper cleaning agents
The use of solvents, cleaning agents, and high-pressure or steam cleaners can damage the system and its components.

  • Only clean the electrical energy storage system with a damp cloth. Use clean water to moisten the cloth.

  • Electrical components must never come into contact with water or cleaning agents.

10.3. Maintenance work

Residual risks:

DANGER DANGER

Risk of death due to improperly performed maintenance work.

  • During maintenance work, troubleshooting and assembly activities, ensure that the product is switched off in a safe manner and secured against being switched on again.

  • Maintenance/servicing work may only be carried out by persons who have attended a detailed training course on the maintenance of the system.

DANGER DANGER

Risk of death from scalding or chemical burns.

Before carrying out maintenance/servicing work on systems which could be under pressure or in which very hot/hazardous substances could still be present:

  1. Wear personal protective equipment against scalding/burns.

  2. Switch off the system.

  3. Secure the system against being switched on again.

  4. Switch off/disconnect loads.

  5. Allow the system to cool down.

  6. Check whether hazardous substances are still in the system.

NOTICE NOTICE

Property damage caused by improperly performed maintenance work.

Maintenance work must only be carried out by trained and qualified specialists.

The frequency of use and environmental conditions can make it necessary to vary the intervals between the activities described below.

  • Instruct the persons responsible for maintaining the product.

  • After consulting the manufacturer, change the maintenance intervals in this documentation.

For maintenance of the inverters and the liquid cooling system, please refer to the documentation of the individual manufacturers and the FENECON maintenance instructions.

10.4. Repairs

Contact the FENECON Service the event of defective components.

11. Storage

Storage up to 3 months
Desiccant bags are used to prevent condensation forming in the container during storage.

There are six desiccant bags in the container on delivery. Replace the saturated desiccant bags with new ones after a storage period of three months and after the container has been open for more than 30 minutes in high humidity or rain.

Remove the desiccant bags after commissioning.

Storage longer than 6 months
Possible consequences: Deep discharge of the cells and battery failure.

  • External charging of the battery modules to nominal voltage — forced charging must be carried out, which is controlled via the FEMS.

This must only be carried out by the manufacturer or by a company commissioned by the manufacturer.

  • Do not store the energy storage system together with flammable or toxic objects.

  • Store energy storage systems with safety defects separately from undamaged systems.

  • The SoC of the individual batteries in the energy storage system is ≥ 25% SoC on delivery.

  • The SoC of the individual batteries should be within a range of 25 to 75 %. If this is not the case, charge or discharge the batteries accordingly.

  • Recharging the batteries is recommended from an SoC of <25 %.

Storage area: Fireproof indoors/outdoors with suitable weather protection

  • Air temperature: -20 °C to 40 °C.

  • Relative humidity: max. 50 % at +40 °C.

11.1. Commissioning instructions — Room air conditioning

Rev. 01 — Status: October 2025

11.1.1. General

NOTICE NOTICE

Risk of damage to the storage system due to improper storage

  • Ensure that the room air conditioning is connected and in operation during all storage and temporary storage of the electricity storage system Industrial XL.

    • A separate, customer-side connection is required for this.

11.1.2. Installation site

  1. Open the front of the container for installation.

  2. The cooling system is located on the left-hand container wall.

control cabinet area cooler
Image 40. Position of the air conditioning in the container

11.1.3. Electrical connection

  1. Use a UV/weather-resistant cable with a cross-section of 5 x 1.5 mm2 or 5 x 2.5 mm2 for the electrical connection.

    1. Fuse protection is provided by a three-pole miniature circuit breaker with a B16 A characteristic on the customer side.

  2. Feed the connection cable into the container underneath the cooling system via a cable gland on the flange plate.

aux supply and comm glands
Image 41. Cable glands on flange plate
  1. Locate terminal X1 on the device.

  2. Prepare the room air conditioning for connection.

  3. Connect the room air conditioning to terminal X1.

cooling system connection
Image 42. Connecting the room air conditioning

After the miniature circuit breaker has been racked in, the device automatically starts operation. Manual operation is not required.

12. Utilization load

The service life of the product depends on the service life and maintenance intervals carried out by specialist personnel. The service life is particularly influenced by preventive maintenance and servicing. Timely replacement of wearing parts and appropriate documentation of each activity is therefore crucial for the availability of the product.

All functional safety elements must be replaced in accordance with the number of operating cycles or operating time specified by the manufacturer before the calculated or specified service life is reached.
The manufacturer must be contacted after 20 years at the latest in order to determine the further procedure with regard to revision or replacement.

13. Transport

This section contains information on external and internal transportation of the product.

Transportation is the movement of the product by manual or technical means.

  • Only use suitable and tested lifting gear and hoists for transportation!

  • The product must only be transported using the means of transport specified by the manufacturer.

  • Use the specified transport reinforcements.

Residual risks

DANGER DANGER

Risk of death due to lifted loads!

  • Standing under suspended loads is prohibited!

  • Ensure that all components have sufficient load-bearing capacity!

  • Observe all the manufacturer’s instructions!

  • Only use the transport lugs for clamping down!

  • You must not use the transport lugs for lifting!

DANGER DANGER

Risk of death due to improper transport!

  • Observe all the manufacturer’s instructions!

  • Transportation is carried out by a hazardous goods carrier.

  • The transportation of lithium-ion batteries "UN3536" is subject to the ADR regulations.

  • A Class 9 dangerous goods label must be affixed to all sides of the container during shipment.

  • When transporting batteries, the current laws, regulations and standards must be observed (e. g. German Dangerous Goods Transportation Act (GGBefG)).

DANGER DANGER

Possible equipment damage caused by falling loads!

Before lifting, make sure that

  • all parts are firmly bolted,

  • the transport lugs and shackles have been properly attached,

  • you wear personal protective equipment.

TIP

Check that the parts and outer packaging are in perfect condition.

Legal regulations
The off-site transportation of the product is carried out in accordance with the legal regulations of the country in which the product is transported off-site.

13.1. Safety instructions

  • Transportation is carried out by a hazardous goods carrier.

  • When transporting batteries, the applicable laws, regulations and standards (e. g. Dangerous Goods Transportation Act — GGBefG) must be complied with.
    All necessary authorizations and documents, such as a special permit and a dangerous goods driver’s license (ADR certificate), must be available.
    It must also be ensured that sufficiently tested lashing equipment is available.

  • Upon receipt, check the delivery immediately for completeness and transport damage.

  • Use personal protective equipment (depending on the boundary conditions) (minimum requirement: protective headgear and protective footwear).

  • Disconnect the electrical connections before transport.

  • Before lifting, check that the attachment points and lifting gear are correctly seated.

  • The container should only be transported with a SoC of min. 25 % and max. 50 %.

  • Observe the detailed lifting instructions for correct transportation.

  • The load capacity must be dimensioned so that the mass of the product can be safely accommodated.

  • The size of the transport surface must be dimensioned so that the product can be safely placed and secured on the transport surface.

13.2. Change of location

It is not intended to relocate the system after commissioning.

If a change of location is planned, consult FENECON GmbH beforehand.

The FENECON Industrial XL, fully equipped with battery packs, has a weight of approx. 32,000 kg.

13.3. Transportation process

Means of transportation

A means of transport that meets the following requirements is needed for safe off-site transportation:

  • The load capacity must be dimensioned so that the mass of the product can be safely accommodated.

  • The size of the transport platform must be dimensioned so that the product can be placed safely on the transport platform without falling.

Required aids

The following aids are required for safe off-site transportation:

  • Loading and unloading: Use a crane. Only lift the fully-equipped Industrial XL container using the transport reinforcements provided.

  • Transportation: only by motor vehicle for road transport.

Lifting instructions

  • A crane with a minimum load capacity of 32 tons is required to transport a fully-equipped Industrial XL.

  • When lifting the electrical energy storage system, the Lifting instructions specified by the manufacturer must be observed.

  • Information on weight, center of gravity and dimensions are found in the dimensions and mass sections.

14. Dismantling and disposal

DANGER DANGER

Risk of death due to malfunction.
Malfunction can result in serious injury or death.

  • Before switching off the individual components, observe the specifications and instructions in the operating/assembly instructions of the respective manufacturer.

  • Before switching off the system, make sure that there are no unauthorized persons in the zone of danger.

14.1. Safety instructions

  • The following suitable personal protective equipment must be worn for all work:

    • Protective footwear.

    • Protective gloves, cut-resistant if necessary.

    • Protective eyewear.

  • Only have the electrical energy storage system dismantled by authorized electricians.

  • Dismantling work must only be carried out when the system has been taken out of operation.

  • Before starting disassembly, all components to be removed must be secured against falling, tipping over or moving.

  • Dismantling work must only be carried out when the system is shut down and only by service personnel.

  • The existing attachment points must be used for the system parts to be transported.

  • Observe the disassembly instructions of the component manufacturers (Appendix, Applicable documents).

  • The batteries are removed by service personnel and transported by a hazardous goods carrier.

  • When transporting the battery modules, observe the current laws, regulations and standards (e. g. German Dangerous Goods Transportation Act (GGBefG)).

14.2. Prerequisites

CAUTION CAUTION

Sharp and pointed edges
Injuries to the body or limbs caused by sharp and pointed edges on parts of the system.

  • Always wear suitable protective equipment when working on the system (cut-resistant protective gloves, protective footwear, protective eyewear)!

Before dismantling, disconnect the power supply to the system and secure it against being switched on again.

14.3. Disposal

  • Observe the local regulations and information in the safety data sheets for the disposal of auxiliary and operating materials.

  • For disposal, please also observe the information in the individual operating instructions for the respective components.

  • If in doubt about the disposal method, contact the manufacturer or the local waste disposal company.

14.3.1. Individual parts

After proper disassembly, the dismantled individual parts must be recycled:

  • The electrical energy storage system must not be disposed of with normal household waste.

  • Scrap metallic materials.

  • Send plastic elements for recycling.

  • Dispose of the remaining components sorted according to material properties.

Electrical waste, electronic components, lubricants and other auxiliary materials are subject to hazardous waste treatment and must only be disposed of by authorized specialist companies.

14.3.2. System

Also observe the following points when disposing of the electrical energy storage system or its components as well as the operating and auxiliary materials:

  • Comply with local national regulations.

  • Observe company-specific specifications.

  • Dispose of operating and auxiliary materials in accordance with the applicable safety data sheets.

  • Dispose of the packaging material in an environmentally friendly manner.

Batteries

  • Do not expose the battery modules to high temperatures or direct sunlight.

  • Do not expose the battery modules to high humidity or corrosive atmosphere.

  • Obtain special instructions on the disposal of used batteries by contacting the FENECON Service.

15. Declaration of Conformity

xl declaration of conformity 1
xl declaration of conformity 2

16. Register

16.1. Applicable documents

  • All supplier documentation can be accessed via the item bill of materials.

Table 27. Applicable documents
No. Component Manufacturer documentation

1

Product data sheet

https://docs.fenecon.de/pdfs/industrial/2026/en/MAR1281_FENECON_Produktblatt_In-XL_EN_Web.pdf

2

Lifting instructions

https://docs.fenecon.de/pdfs/industrial/2025/en/INW-501-01_crane-lifting_inverter-rack.pdf
https://docs.fenecon.de/pdfs/industrial/2025/en/IXL-217-01-02_crane-lifting_container.pdf

3

Transport instructions

https://docs.fenecon.de/pdfs/industrial/2025/en/IXL-239-01-01_container_transport.pdf
https://docs.fenecon.de/pdfs/industrial/2025/en/INW-502-01_inverter_rack_transport.pdf

4

Installation concept

https://docs.fenecon.de/pdfs/industrial/2025/en/IXL-351-01-00_installation_concept.pdf

5

Fire protection information

https://docs.fenecon.de/en/industrial/industrial_xl/brandschutz/XL_Brandschutzinformationen.html

6

Supplement to the Ordinance on Installations for Handling Substances Hazardous to Water (AwSV)

https://docs.fenecon.de/en/industrial/industrial_xl/awsv/XL_AwSV.html

7

Warranty conditions

https://docs.fenecon.de/pdfs/industrial/2025/en/V202509_EN_Garantiebedingungen_FENECON_Industrial_L-XL.pdf

8

Sound pressure

https://docs.fenecon.de/en/industrial/industrial_xl/schallschutz/XL_Schallschutzinformationen.html

9

Battery

cf. "Battery" Section of these Operating Instructions

10

Inverter KACO blueplanet gridsave 92.0 kVa

https://kaco-newenergy.com/index.php?eID=dumpFile&t=f&f=19743&token=480cf790aab1a3af6d22ec8aac872281e9ae3076:
https://kaco-newenergy.com/products/blueplanet-gridsave-920-137-tl3-s

11

HYDAC Cooling system

https://www.hydac.com/shop/en-ch/4570230

12

Router MikroTik
RB5009UG+S+IN

https://mikrotik.com/product/rb5009ug_s_in#fndtn-downloads

13

Room air conditioning

Safety data sheet for auxiliary and operating materials:
https://www.rittal.com/pdf-creator/variant/de-de/3188340
https://www.rittal.com/imf/none/3_11369/3188340_Anleitung_ndash_R_513A_DE
https://www.rittal.com/imf/none/3_9033/3188340_Sicherheitsdatenblatt_K_auml_ltemittel_ndash_R_513A_DE

14

Block diagram

https://docs.fenecon.de/pdfs/industrial/2025/en/Industrial_XL_block_diagram_EN.pdf

15

Network diagram

https://docs.fenecon.de/pdfs/industrial/2025/en/Industrial_XL_network_plan_EN.pdf