Installation and Configuration Manual — FEMS Package 3-Phase Sensor 80 A (SOCOMEC COUNTIS E23/E24)

1. Introduction

Unless stated otherwise, the information contained in these documents is the property of FENECON GmbH. Publication, in whole or in part, requires the written consent of FENECON GmbH.

These instructions do not claim to be complete or correct. It merely serves as an abridged version of the original SOCOMEC instructions. These can be found at here.

Subject to changes and printing errors!

1.2. Qualification of the installer

A qualified installer is a person who has the following experience and training:

  • Setting up, switching on, switching off, disconnecting, earthing, short-circuiting and repairing circuits and devices

  • Standard maintenance and use of protective devices in accordance with current safety standards

  • First aid/emergency care

  • Current knowledge of local regulations, standards and guidelines

1.3. Symbols used

Attention
Important information
Danger

1.4. Dangers and safety instructions

The Socomec Countis E23/E24 must be installed by a qualified specialist.

The manufacturer’s installation and service instructions must be observed.

2. Product description

2.1. Scope of delivery

After you have received the delivery, check that all components have been included. Inspect the scope of delivery for damage. If anything is missing or damaged, please contact the supplier immediately. The following components are included in the delivery:

2.2. Model overview

COUNTIS E23 and E24 are modular active and reactive energy meters that count and display the energy consumed. They are designed for three-phase grids and allow direct connection up to 80 A. They are equipped with a MODBUS communication bus. The COUNTIS E23 and E24 are identical in construction. The E24 is the MID version of the E23.

Socomec Countis E23 E24 Uebersicht beschriftet

3. Connection

The meter is electrically connected through the 3 phases and the neutral conductor in accordance with the original instructions. The meter has an input and output for connecting the phases. If these are connected incorrectly, the meter may later output a negative value in Online Monitoring.

3.1. Screw connection

Socomec Countis E23 E24 Verdrahtung
Figure 1. Screw connection

3.2. Connection to a generator

Socomec Countis E23 E24 Anschluss Erzeuger
Figure 2. Connection — Generator

3.3. Connection to the meter of the metering point operator

Socomec Countis E23 E24 Anschluss Stromnetz
Figure 3. Connection — Meter to metering point operator

3.4. Connection to a consumer load

Socomec Countis E23 E24 Anschluss Verbraucher
Figure 4. Connection — Consumer load

4. Communication

The Modbus communication available with COUNTIS E23/E24 takes place via a serial RS485 interface (2 or 3 wire), which enables the device to be operated from FEMS. In the standard configuration, 32 devices can be connected to a PC or a controller over 1200 meters using an RS485 interface.

Socomec Countis E23 E24 RS485 beschriftet
Figure 5. RS-485 wiring
  1. COM RS-485 connection from FEMS

  2. Data conductor minus (-) (B conductor)

  3. Data conductor plus (+) (A conductor)

  4. Minus (-) contact

  5. Plus (+) Contact

To connect several meters in series, the RS-485 connection must be looped through, as shown in the figure below.

Note the connection of the terminating resistor (120 Ω)!

1500
Figure 6. Looping through the RS-485 wiring

If the supplied RS485 cable is not long enough, we recommend using a LiYCY with a cross-section of 0.5 mm². This is suitable for max. 500 m. In general, the manufacturer’s specifications and recommendations must be observed.

5. Overview of controls

Socomec Countis E23 E24 Neu
Figure 7. Control elements
  1. SET button

  2. Cursor key UP (^)

  3. ENTER button

  4. LED operating control

  5. LCD screen

  6. Three-phase network connection

  7. Details of MID certification (if available)

  8. Neutral conductor connection

6. Configuration

The following configuration settings must be used for use with FEMS:

Baud rate for communication

9.6

RS-485 Modbus address — Grid connection point

005

RS-485 Modbus address — PV generation

006

RS-485 Modbus address — Other generators/consumers

007…​246

Follow the installation and service instructions for the meter installed to make the settings. The following steps are for simplification purposes only.

6.1. Opening the programming mode

  1. Press the ENTER button to switch between the menu items within the configuration menu until the SETUP menu item appears.

Socomec Countis E23 E24 Setup
  1. Then press and hold the ENTER button for three seconds to enter programming mode.

Socomec Countis E23 E24 Setup 1

6.2. Input — RS-485 Modbus address (Addr)

The following steps describe the procedure for configuring the RS-485 Modbus address.

  1. Press the ^ button until the menu for setting the address appears

Socomec Countis E23 E24 Setup Addr 8
  1. Press the ENTER button. The left-hand digit then flashes

Socomec Countis E23 E24 Setup Addr 1
  1. Press the ^ button until the value of the left-hand digit is set to 0.

Socomec Countis E23 E24 Setup Addr 2
  1. Press the ENTER button. The middle digit then flashes.

Socomec Countis E23 E24 Setup Addr 3
  1. Press the ^ button until the value of the middle digit is set to 0.

Socomec Countis E23 E24 Setup Addr 4
  1. Press the ENTER button. The right-hand digit then flashes.

Socomec Countis E23 E24 Setup Addr 5
  1. Press the ^ button until the value of the right-hand digit is set to 5.

Socomec Countis E23 E24 Setup Addr 6
  1. Press the ENTER button to save the entries.

Socomec Countis E23 E24 Setup Addr 7

6.3. Communication speed (baud rate)

The following steps describe the procedure for configuring the baud rate.

  1. Press the ^ button. The menu item for setting the baud rate appears.

Socomec Countis E23 E24 Setup Baudr 1
  1. Press the ENTER button. The baud rate value then flashes.

Socomec Countis E23 E24 Setup Baudr 2
  1. Press the ^ button to switch between the different baud rate values. Select the value 9.6.

Socomec Countis E23 E24 Setup Baudr 3
  1. Press the ENTER button to save the entry.

Socomec Countis E23 E24 Setup Baudr 4

6.4. Communication parity

The following steps describe the procedure for configuring the communication parity.

  1. Press the ^ button. The menu item for setting the communication parity appears.

Socomec Countis E23 E24 Kom Paritaet 1
  1. Press the ENTER button. The communication parity value then flashes.

Socomec Countis E23 E24 Kom Paritaet 2
  1. Press the ^ button to switch between the different values. Select the value n (none).

Socomec Countis E23 E24 Kom Paritaet 1
  1. Press the ENTER button to save the entry.

Socomec Countis E23 E24 Kom Paritaet 3

6.5. Communication stop bit

The following steps describe the procedure for configuring the communication stop bit.

  1. Press the ^ button. The menu item for setting the communication stop bit appears.

Socomec Countis E23 E24 Kom Stop 1
  1. Press the ENTER button. The communication parity value then flashes.

Socomec Countis E23 E24 Kom Stop 2
  1. Press the ^ button to switch between the different values. Select the value 1.

Socomec Countis E23 E24 Kom Stop 1
  1. Press the ENTER button to save the entry.

Socomec Countis E23 E24 Kom Stop 3

6.6. Exiting programming mode

  1. Press and hold the ENTER button for three seconds. The "SAVE" menu then flashes with the value "y" (YES). This means that the entries will be saved. If you want to discard the entries, press the ^ button to go to the value "n" (NO)

Socomec Countis E23 E24 Save 1
  1. Press the ENTER button to confirm the entry.

Socomec Countis E23 E24 Save 2

The configuration of the meter is now complete. Proceed in the same way to configure other meters. Please note the different RS485 Modbus addresses.

7. Diagnostic messages

The following diagnostic messages are displayed if there are connection errors or faults

7.1. Missing phases

If one or more phases are not recognized, the exclamation mark flashes at the top left of the display.

Socomec Countis E23 E24 Diagnose 1

7.2. Swapped phases

If a 123 phase sequence is detected, the arrow appears clockwise on the display.

Socomec Countis E23 E24 Diagnose 2

If a 132 phase sequence is detected, the arrow appears at the top of the display, rotating to the left.

Socomec Countis E23 E24 Diagnose 3

7.3. Malfunction

If the message ERR appears on the display, there is a measuring device fault and the measuring device must be replaced.

Socomec Countis E23 E24 Diagnose 4

8. Troubleshooting

Causes

Solutions

Device switched off

Check neutral conductor and phase 1 cable connections

Phases not shown on the display

Check connections

Phases reversed on the display

Check network configuration

Error message

Check whether meter is working properly

The configuration is now complete.